Model | SunC2- 3.6LV01(W/B) | SunC2- 5.0LV01(W/B) | SunC2- 6.0LV01(W/B) | SunC2- 7.0LV01(W/B) | SunC2- 8.0LV01(W/B) |
Battery Input Data |
| ||||
Battery Type | Lead-acid or Lithium-ion | ||||
Battery Voltage Range | 40-60V | ||||
Max. Charging Current | 90A | 120A | 135A | 175A | 190A |
Max. Discharging Current | 90A | 120A | 135A | 175A | 190A |
Charging Strategy for Li-ion Battery | Self-adaption to BMS | ||||
Number of Battery Input | 1 | ||||
PV String Input Data |
| ||||
Max. PV Access Power | 7200W | 10000W | 12000W | 14000W | 16000W |
Max. PV Input Power | 5760W | 8000W | 9600W | 11200W | 12800W |
Max. PV Input Voltage | 500V | ||||
Start-up Voltage | 125V | ||||
MPPT Voltage Range | 150-425V | ||||
Rated PV Input Voltage | 370V | ||||
Max. Operating PV Input Current | 18+18A | 32+32A | |||
Max. Input Short-Circuit Current | 27+27A | 48+48A | |||
No. of MPP Trackers / No. of Strings MPP Tracker | 2/1+1 | 2/2+2 | |||
AC Input/Output Data |
| ||||
Rated AC Input/Output Active Power | 3600W | 5000W | 6000W | 7000W | 8000W |
Max. AC Input/Output Apparent Power | 3960VA | 5500VA | 6600W | 7700VA | 8800VA |
Peak Power (off-grid) | 2 times of rated power, 10s | ||||
Rated AC Input/Output Current | 16.4/15.7A | 22.8/21.8A | 27.3/26.1 | 31.9/30.5A | 36.4/34.8A |
Max. AC Input/Output Current | 18/17.3A | 25/24A | 30/28.7 | 35/33.5A | 40/38.3A |
Max. Continuous AC Passthrough (Grid to Load) | 35A | 40A | 50A | ||
Rated Input/Output Voltage/Range | 220V/230V 0.85Un-1.1Un | ||||
Grid Connection Form | L+N+PE | ||||
Rated Input/Output Grid Frequency/Range | 50/45-55Hz 60/55-65Hz | ||||
Power Factor Adjustment Range | 0.8 leading-0.8 lagging | ||||
Total Current Harmonic Distortion THDi | <3% (of nominal power) | ||||
DC Injection Current | <0.5% In | ||||
Efficiency |
| ||||
Max. Efficiency | 97.6% | ||||
Euro Efficiency | 96.5% | ||||
MPPT Efficiency | >99% | ||||
Protection |
| ||||
Integrated | DC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Overvoltage Load Drop Protection, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (optional), Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch, DC Terminal Insulation Impedance Monitoring, Residual Current (RCD) Detection, Surge protection level | ||||
Surge Protection Level | TYPE II(DC), TYPE II(AC) | ||||
Interface |
| ||||
Display | LCD+LED | ||||
Communication Interface | RS485/RS232/CAN | ||||
Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | ||||
General Data |
|
Operating Temperature Range | -40 to +60°C, >45°C Derating |
Permissible Ambient Humidity | 0-100% |
Permissible Altitude | 2000m |
Noise | <30dB |
Ingress Protection (IP) Rating | IP65 |
Inverter Topology | Non-Isolated |
Over Voltage Category | OVC II(DC), OVC III(AC) |
Cabinet Size (WxHxD) | 366x630x281.41mm (Excluding Connectors and Brackets) |
Weight | 27.1kg |
Type of Cooling | Intelligent Air Cooling |
Warranty | 5 years (10 years when installed with a Sunsynk battery) |
Grid Regulation | G98/G99, NRS 097-2-1, EN 50549-1 |
Safety / EMC Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |