With the Elite Battery separated from the Power Distribution Unit (PDU) identify Pins 6 and 7 of the 12-pin BMS Connector. Note that Pin 6 is the 1st Pin on this BMS socket and the Large Connectors are labelled 1 to 5

Using a short piece of single core CAT-6 cable (or similar) with the ends bared, insert each end into Pins 6 and 7 to create a shorting link, as per image above. This will enable SWA and SWB to activate the Battery. With a DC Voltmeter now measure the Voltage between the Positive and Negative Connector Ports of the Battery as per image below.

A Good Battery should measure 50V+
A Low Battery will measure 41V to 49V
A Depleted Battery will measure 38V to 41V and should be able to be recharged by the Inverter using AGMV.
For any Voltage below 38V please call Sunsynk UK Support on the UK number below to obtain a Ticket Reference #???? and further assistance / guidance with your Over Depleted Battery.
0151 832 4300